Four workers were treated for minor injuries after the explosion at the Torrance, Calif., refinery. The explosion

Cal/OSHA Cites ExxonMobil Refining & Supply After Torrance Explosion

The agency issued 19 citations and $566,600 in proposed penalties, with 18 of the citations classified as serious.

Cal/OSHA on Aug. 13 issued 19 citations to ExxonMobil Refining & Supply Company for safety and health violations following the agency's investigation into the Feb. 18, 2015, explosion at the company's Torrance refinery. Four workers were injured; the proposed penalties total $566,600.

Cal/OSHA classified 18 of the citations as serious "due to a realistic possibility of worker death or serious injury," with six of those serious violations also classified as willful because Cal/OSHA found the company did not take action to eliminate known hazardous conditions at the refinery and intentionally failed to comply with state safety standards. ExxonMobil Refining & Supply has 15 working days to appeal the citations to the Occupational Safety and Health Appeals Board.

"Petroleum refineries have the responsibility to keep workers safe and to also protect nearby communities and the environment," said Christine Baker, director of the California Department of Industrial Relations. She said the investigation "revealed severe lapses in Exxon's safety protocols."

The explosion resulted from a hydrocarbon release from the refinery's fluid catalytic cracker unit into its electrostatic precipitator, which exploded. Eight workers were decontaminated after the incident and four were treated for minor injuries.

Cal/OSHA said the investigation concluded that:

  • A 2007 safety review uncovered concerns about flammable vapor leakage in the precipitator, and management knew of potential fire or explosion hazards from the leakage but did not correct the danger.
  • ExxonMobil Refining & Supply's incident response team, which included senior management, was aware of a leaking spent slide valve on the FCC unit before the explosion occurred.
  • The FCC unit had not been working properly for as many as nine years prior to the incident, and there was no functional pressure transmitter, so the company was unable to monitor hydrocarbon pressure buildup inside the unit.
  • There was no written operating procedure for placing the FCC unit in hot standby.

Cal/OSHA issued an order prohibiting use of the FCC unit on Feb. 18. The order remains in effect until ExxonMobil Refining & Supply can demonstrate that the unit is safe to operate.

Product Showcase

  • EMSL Analytical, Inc. - Air Sampling Supplies & Testing Labs

    EMSL Analytical, Inc. operates laboratories throughout the United States and Canada. EMSL is a nationally recognized and locally focused provider specializing in fast laboratory results for Asbestos, Mold, Silica, Lead & Metals, Bacteria, Legionella, USP , Combustion By-Products, VOC’s, Radon, PCB’s, Formaldehyde, METH/Fentanyl, Identification of Dust & Unknowns. Sampling Pumps, Cassettes, Media & Supplies available. Reach us at 1-800.220.3675 Read More

  • The MGC Simple Plus

    The MGC Simple Plus is a simple-to-use, portable multi gas detector that runs continuously for three years without being recharged or routinely calibrated after its initial charge and calibration during manufacturing. The detector reliably tests a worksite’s atmosphere for hydrogen sulfide, carbon monoxide, oxygen and combustible gases (LEL). Its durability enables the detector to withstand the harshest treatment and environments, hence earning it an IP 68 rating. The MGC Simple Plus is also compatible with a variety of accessories, such as the GCT External Pump. Visit gascliptech.com for more information. Read More

  • Glove Guard® Clip

    Safety should never be compromised, especially when it comes to proper glove usage. The Glove Guard® clip enhances safety by encouraging employees to keep their gloves with them at all times. This reduces the risk of accidents and injuries on the job. By ensuring everyone has their gloves readily available, we help promote a culture of safety and efficiency. The Glove Guard® clip is designed to withstand the toughest work environments. Constructed from robust materials made in the USA, it can endure extreme conditions, including harsh weather, and rigorous activities. Read More

Featured

Artificial Intelligence