The OSHA document recommends complying with the ANSI standard, Z358.1-2014, which says plumbed systems should be activated weekly, to eliminate these hazards.

OSHA Warns of Contaminated Eyewash Water

A recent OSHA Infosheet highlights the risk of eye infections from contaminated water in improperly maintained emergency equipment.

OSHA's recent Infosheet highlights the infection hazards that may be present when emergency eyewash stations are improperly maintained. Eyewash facilities are required in workplaces where corrosive chemicals are used (29 CFR 1910.151(c)) and in HIV and HBV research laboratories and production facilities (1910.1030(e)(3)(i)) and "where there is any possibility that an employee’s eyes may be splashed with solutions containing 0.1 percent or greater formaldehyde (1910.1048(i)(3))," while research and production laboratories and medical facilities also may have them.

"How can improperly maintained eyewash stations cause infections? Water found in improperly maintained eyewash stations is more likely to contain organisms (e.g., Acanthamoeba, Pseudomonas, Legionella) that thrive in stagnant or untreated water and are known to cause infections," it states. "When a worker uses an eyewash station that is not maintained, organisms in the water may come into contact with the eye, skin, or may be inhaled. Workers using eyewash stations after exposure to a hazardous chemical or material may have eye injuries that make the eye more susceptible to infection. Also, workers with skin damage or compromised immune systems (e.g., transplant recovery, cancer, lupus) are at increased risk for developing illnesses from contaminated water."

The document recommends complying with the ANSI/ISEA standard, Z358.1-2014, which says plumbed systems should be activated weekly to eliminate these hazards.

"Self-contained eyewash units must be maintained and employers should consult the manufacturer's instructions for maintenance procedures. This includes flushing the system and using only solutions appropriate for flushing eyes," the document states.

Product Showcase

  • Magid® D-ROC® GPD412 21G Ultra-Thin Polyurethane Palm Coated Work Gloves

    Magid’s 21G line is more than just a 21-gauge glove, it’s a revolutionary knitting technology paired with an advanced selection of innovative fibers to create the ultimate in lightweight cut protection. The latest offering in our 21G line provides ANSI A4 cut resistance with unparalleled dexterity and extreme comfort that no other 21-gauge glove on the market can offer! Read More

  • Safety Shower Test Cart

    The Safety Shower Test Cart speeds up and simplifies emergency shower tests, ensures you stay in compliance with OSHA regulations, and significantly reduces testing costs. With 7 unique features, the cart makes testing easy, effective, and efficient. You can test water clarity, flow, temperature, and spread—all at the same time! Most safety shower testing kits create a mess, take too much time to use, and don't fully help you stay in compliance with OSHA & ANSI standards. Transform the way you test emergency showers with Green Gobbler Safety. Read More

  • Matrix's OmniPro Vision AI Collision Avoidance System

    OmniPro Vision AI is a state-of-the-art collision avoidance system that features NIOSH award-winning Visual Artificial Intelligence (AI) technology. This highly accurate, powerful system identifies and alerts on pedestrians, vehicles and specified objects, ensuring safer facilities, mining operations and industrial sites. With its web-based cloud application, OmniPro Vision AI also logs and analyzes a wide range of data related to zone breach notifications. Operating without needing personal wearable devices or tags, OmniPro has visual and audible zone breach alerts for both operators and pedestrians. Read More

Featured

Artificial Intelligence