High Tech at Low Cost

Computer simulation helped reduce a laboratory's chlorine concentration to minimal levels while avoiding the cost of testing alternate exhaust systems.

WORKERS throughout a wide range of chemical processing industries are becoming more conscious than ever before of discharges that, although they fall within acceptable safety limits, cause annoyance and potential discomfort. The approach of redesigning process equipment in order to eliminate the discharges at the source is the ideal solution in the case where the process is being overhauled for other reasons, but otherwise it is often too costly to consider.

The more practical approach usually is to retrofit an exhaust system to the existing equipment to remove as much of the contaminants as possible before they are circulated through the plant. This approach, however, also has its challenges.

Facilities management planned to install an exhaust system to eliminate chlorine odor but were uncertain how the exhaust system should be configured to have the greatest impact. It would have been very expensive to install the exhausts in several different locations in order to see which configuration worked best. Hence the management hired a consulting firm to use computational fluid dynamics (CFD) to simulate the performance of the most likely design alternatives. The consultant analyzed four different cases and found which one worked best. The chemical company installed the exhaust system based on these guidelines and discovered the new system completely solved the problem.

Traditional Approach Involves Cost, Disruption
Exhaust system performance is highly dependent upon a number of variables, such as the flow and pressure conditions inside the plant, the distribution of the various sources of contaminants, and the placement and capacity of the exhaust system. But it is impractical to measure the flow and pressure to any significant degree of accuracy, so the best engineers can do in most cases is make a rough hand calculation or educated guess as to which configuration will work best.

The accuracy of hand calculations is reduced by several factors. First, these calculations don't take the geometry of the structure into account. Second, they determine only average chemical concentrations but not the spatial distribution or gradients in the distribution, both of which are important.


If the design does not meet the requirements, then it becomes necessary to perform a costly and, at times, disruptive series of experiments.
The result is that engineers are unable to be certain about the performance of a prospective design until the ventilation system is installed and tested. Usually, such a system is installed, the concentration of the contaminants is measured, and the performance of the system is assessed. If the design does not meet the requirements, then it becomes necessary to perform a costly and, at times, disruptive series of experiments, modifying the design and evaluating its performance until the design criteria are satisfied.

Simulating Airflow in Software
CFD can dramatically improve this process by predicting airflow, pressure, and chemical concentrations throughout a region with a high level of accuracy. CFD uses numerical methods to solve the fundamental nonlinear differential equations that describe fluid flow (the Navier-Stokes and allied equations) for predefined geometries, boundary conditions, process flow physics, and chemistry. The result is a wealth of predictions for flow velocity, temperature, density, and chemical concentrations for any region where flow occurs.

CFD is a very potent, non-intrusive, virtual modeling technique with powerful visualization capabilities. A key advantage of CFD is that engineers can evaluate the performance of a wide range of exhaust system configurations on the computer without the time, expense, and disruption required to make actual changes on site.

The CFD software package selected for this project is specially designed to simplify the process of modeling ventilation systems. It is an easy-to-use design tool that simplifies the application of state-of-the-art CFD technology to the design and analysis of ventilation systems, which deliver indoor air quality, thermal comfort, health and safety, air conditioning, and contamination control. The software is also useful for understanding external flows around buildings and how external airflow impacts natural ventilation inside buildings.

The ability to rapidly create and automatically mesh ventilation system problems (using real rather than compromised geometries) is coupled with a fast, accurate, and well-proven unstructured solver engine. Simulation time is reduced through the use of object-based model building with predefined objects, such as rooms, people, fans, partitions, vents, openings, walls, sources, resistances, ducts, and hoods.

Modeling the Laboratory
On this project, the engineers worked with floor plans provided by the chemical laboratory, direct measurements and observations, and photos taken in the lab. The computational domain covered an area 131 feet long, 24 feet high including 4 feet under the floor, and 126 feet deep. They created a CFD model that used about 850,000 cells to reproduce the geometry of open space within the plant. The model took about 10 hours to solve on a fast personal computer.

An air balancing report was provided that measured air moving in and out of the laboratory at various locations. The boundary conditions were created based on this report. Chlorine sources were located in the sump area, trench area, and on the surface of three tanks. The laboratory itself provided measurements on the volume of chlorine emitted by the various sources in the plant. The values for chlorine were not accurate enough to determine absolute values for chlorine concentration but were sufficient to meet the objectives of this study by determining the relative performance of various design alternatives. A conventional turbulence model was used.

The consultants decided to focus first on the sump and trench, which were the largest sources of chlorine, so they turned off the other sources of chlorine in the model. Based on experience, the chemical company's engineers suggested two exhaust system configurations they thought had the best chance of succeeding in this difficult area of the problem. Each configuration used four 200 cfm exhausts for the trench and one for the sump.

In the first case the exhausts were located under covers that were positioned on top of the trench and sump, while in the second they were located above the trench and sump covers. The consultants then ran the simulation and generated color-coded plots that showed the concentration of chlorine predicted by the simulation throughout the plant at a height of 4 feet, 6 feet, and 8 feet. The results of these simulations showed that placing the exhausts under the covers provided slightly better results.

Evaluating Conditions with All Sources On
With this key point established, engineers moved on to evaluate the effects of adding the other sources. They positioned exhausts under the covers of the sumps and trenches, the design that was shown to be best from the earlier simulation. Then they added additional 400 cfm exhausts above the three tanks while varying the gap between the top of the tank and the exhaust at 2 feet and 4 feet.

The results of these simulations showed that placing the exhausts 2 feet above the tanks provided superior results.

In their final report, the consultants recommended that the exhausts be positioned 2 feet above the surfaces to maintain chlorine concentration at minimal levels as predicted by the simulation, with the sump and trench exhausts located under the covers and the tank exhausts. The color graphic output provided by the simulation made it relatively easy to make the case for the optimized design to laboratory management.


Having a validated design provided confidence that the new configuration could be installed without the need for downstream changes.
Having a validated design provided confidence that the new configuration could be installed without the need for downstream changes that would have otherwise increased the cost and disruption involved in the changes. When the new exhaust system was installed, reports from the site indicated workers could no longer smell chlorine in the plant. The laboratory's managers believe they have successfully accomplished their objective of reducing chlorine concentration to unobjectionable levels at the lowest possible cost.

This article appeared in the January 2005 issue of Occupational Health & Safety.

This article originally appeared in the January 2005 issue of Occupational Health & Safety.

Product Showcase

  • SlateSafety BAND V2

    SlateSafety BAND V2

    SlateSafety's BAND V2 is the most rugged, easy-to-use connected safety wearable to help keep your workforce safe and help prevent heat stress. Worn on the upper arm, this smart PPE device works in tandem with the SlateSafety V2 system and the optional BEACON V2 environmental monitor. It includes comprehensive, enterprise-grade software that provides configurable alert thresholds, real-time alerts, data, and insights into your safety program's performance all while ensuring your data is secure and protected. Try it free for 30 days. 3